Model | TPV |
Output | 333mV rms |
Rated ratio | 100A 600A 1000A 3000A 6000A |
Read Accuracy | 0.5% typical at 1%(≥10A) to 110% of rated Current @25℃ |
Phase error | ≤0.5° |
Linearity | ±0.2% of reading (10% to 120% of range) |
Bandwidth | 30Hz to 5kHz |
Maximum Burden | 0.5Ω(each phase) |
Measurement | Secondary CTs to measure output of integrator |
Power consumption | 8W |
Output on 0A (zero drift) | ≤0.01A |
Temperature drift | 200ppm/℃ |
Weight | 20g |
Dimension | 114*100*22.5mm |
Power supply | 24V DC |
Operating temperature | -20℃ to 70℃ |
Storage temperature | -30℃ to 90℃ |
Relative humidity | 80% max. without condensation |
Protection degree | IP20 |